Trustworthiness Guide
This page is a draft
This page documents the known and potential reliability risks of our solutions and the measures in place to mitigate them. Its purpose is to provide a structured, up-to-date view of factors that may affect system trustworthiness, covering assumptions, limitations, operational risks, and residual risks. The document serves as a living reference to support design decisions, deployments, and continuous improvement in reliability.
This page is created in response to our Solutions Roadmap published in 2023, where maintaining a documented view of reliability risks was explicitly identified as an action item under the reliability pillar. It fulfills that commitment by formalizing the envisioned “trustworthiness guide” and translating the roadmap intent into a concrete, maintained reference.
The document is structured in a Q&A format, with each entry framed as a what-if question to systematically explore potential failure modes, edge cases, and misuse scenarios. This approach is intended to make risks explicit, actionable, and easier to review across design, deployment, and operational contexts.
Risks
Physical connection to the controller breaks
The physical connection between the Safety AI and the controller can break due to cable cuts or abrasion, loose or improperly tightened terminals, connector disengagement, vibration, or loss of supply power affecting the relay circuit. If such a break is not explicitly detected, the controller may continue to assume that the last received signal remains valid, potentially allowing operation to continue despite the absence of a reliable safety indication.
Mitigation / solution
Use a normally closed (NC) relay contact to signal safety status.
With an NC contact, the circuit is closed in its default, unpowered state. The Safety AI must actively energize the relay to change this state. Any interruption—such as cable damage or loss of power—causes the relay to automatically return to its default state, ensuring that a broken connection cannot be interpreted as a valid safe condition.
Relay contacts weld or get stuck
Relay contacts may weld or get stuck due to electrical arcing, excessive current, mechanical wear, or contamination. When this occurs, the relay may no longer change state in response to control signals, causing the controller to receive a constant indication regardless of the actual safety condition. This can prevent unsafe situations from being correctly signaled.
Mitigation / solution
Use dual-channel relay signaling with independent contacts and plausibility checking at the controller.
By using two separate relay paths driven independently and requiring consistent state changes, welded or stuck contacts can be detected through disagreement or lack of transition. This turns a latent fault into a detectable one.
Both channels could get stuck if they share a common cause, such as the same relay, the same power supply, identical load stress, or the same environmental conditions. This is why channels must be independent (separate contacts, relays, wiring, and ideally power) to meaningfully reduce the risk.