Jump to content

IPIO Datasheet

From Event Gates Wiki
IPIO

This is a draft

Communications
Interface Ethernet
LAN 1-port 10/100Base-T(X)
Channels
Input 4 Digital
Input type Voltage-driven digital input
Input interface Optocoupler-based input stage
Optocoupler component isolation 5 kVrms input-to-output isolation for 1 minute
Output 8 Digital
Output type Solid-state sourcing voltage output
Output voltage Tracks the applied field supply voltage
Recommended application range 12-24 VDC systems
Protected continuous output current Up to 200 mA per channel
Output device class G3VM-61D1 type SSR, 60 V load voltage, 500 mA element rating
Pulse interval Firmware configurable
Derived pulse timing capability SSR tON = 0.8 ms typ / 2.0 ms max, tOFF = 0.1 ms typ / 0.5 ms max
Recommended pulse rate Conservative publication candidate <= 200 Hz for low-frequency signaling
Application note Outputs are voltage outputs, not dry contacts. Use an external relay if dry-contact behavior or higher-power switching is required.
Power
Input 12-24VDC
Derived input current @ 12 VDC Approximately 70 to 100 mA, excluding external output loads
Derived input current @ 24 VDC Approximately 35 to 50 mA, excluding external output loads
Additional current per asserted DI Approximately 2.8 mA @ 12 VDC, 5.8 mA @ 24 VDC when driven from the module supply domain
Connectors
Input 1x4 plug-in screw terminal block
Output 1x8 plug-in screw terminal block
Power 1x2 plug-in screw terminal block
Terminal pitch 3.5 mm
Leds
Output 8 blue
Input 4 blue
System 1-

2-Emergency

Software
Connection TCP
Interface IPIO Manager
UAC Username/Password [1]
General
Dimensions 110x83x30 mm (without rail adaptor)
Weight 202 g
Package Cardboard box (13x18x8 cm)
Mounting DIN-Rail mount
Certification CE, Rohs

Notes

  1. ↑ IPIO has 2 default users defined, one for VIS access and one for administration.